Closed JSC “Electrovypryamitel-Works of special transformers”

              
                                                                                                                                                                                               

Explosion-proof units designed for operation under explosive atmosphere of type

ÂÒÏÅ-200-230ÓÕË4

       They are installed in mines, underground mine working, on gas-distribution stations and etc. They provide for proper operation under explosive atmosphere.

        

Operation conditions.

Climatic environmental factors:

 

- ambient temperature upper value is 308 K (35C);

 

- ambient temperature lower value is 263 K (minus 10C);

 

- relative humidity upper value is 98% at temperature of 308 K (35C);

 

- the rectifier should provide for reliable and stable operation after being in inoperative state at temperature ranging from 233 to 333 K (from minus 40 to plus 50C).

 

 

The rectifier mass (gross) in shipping container, max. 3300 kg.

Overall dimensions (width x depth x height) - 1476 x 1472 x 2304 mm.

Basic parameters: 

Parameter name 

 Rating 

 1. A.c. supply mains:

 

- voltage, V

- frequency, Hz

- number of phases

- power consumed from supply mains kVA, max

 

 

380

50

3

78

2. Output parameters:

 

- rated voltage, V

- rated current (root-mean-square value), A

- limits of manual controlled of setting of charging current stabilization (of root-mean-square value), A 

- ranges of manual controlled setting of voltage limiting during storage battery boost charge, V

- ranges of manual controlled setting of battery charging time with

discreteness of 1 h, h 

- rated output power, kW

- power factor under rated mode, min

- tolerable setting deviations of voltage limiting during storage battery boost charge, %, max.

- setting tolerable deviations of charging current stabilization, %, max 

 

 

 

230

200

îò 40 äî 200 

îò 46 äî 230

 

îò 1 äî 10

46

0,7

 ±5

 ±2

3. Efficiency under rated conditions, %, min

85

 4. Insulation electric resistance:

- under rated climatic conditions, ÌÎm, min

- under ambient temperature upper value after operation under rated mode, ÌÎm, min.

- after being at relative humidity of (98±2)% and ambient temperature of 308 K (35C) for 10 days, ÌÎm, min.

 

20

5 

 0,5