Charging-power rectifiers
Static converters (rectifiers) for batteries charging and power loads supply
Supply mains parameters |
Output parameters |
Unit type |
Frequency, Hz |
Voltage, V |
Phases number |
Ð,
kW |
I rat.,
À |
U rat.,
B |
Current change range, (À) |
Voltage change range, (V) |
Current stabilization accuracy, (%) |
Voltage stabilization accuracy,(%) |
Current ripple factor, (%) |
Remark |
ÂÀÊÑ-2,75-27 |
50 |
380 |
3 |
2,75 |
102 |
27 |
0,3-102 |
25-30 |
|
±2 |
3 |
to supply power loads |
ÎÏÑ-125 |
50 |
220 |
1 |
0,125 |
8 |
15,6 |
1-8 |
4-16
4-14 |
±7
|
±5 |
10 |
charging duty
buffer
duty |
ÎÏÑ-800 |
50 |
220 |
1 |
0,8 |
20 |
40 |
4-20 |
24-40
24-36 |
±7
|
±5 |
10 |
charging duty
buffer
duty |
ÂÀÊ-2-28,5Ì1 |
50 |
220 |
1 |
2 |
55,6 |
28,5 |
5,5-55,6
5,5-61 |
27-30
12-36 |
±5 |
±2
±2 |
8
|
power
duty
charging duty |
ÂÀÊ-6-28,5Ì1 |
50 |
220 |
1 |
6 |
166,5 |
28,5 |
16,6-166,5
16,6-183 |
27-30
12-36 |
±5 |
±2
|
8
|
power
duty
charging duty |
ÂÀÊ-12-28,5Ì1 |
50 |
220 |
1 |
12 |
330 |
28,5 |
33-330
33-363
100-390 |
27-30
12-36
25-75 |
±5
±5 |
±2
±2
±2 |
8
|
power
duty
charging duty
"welding duty" |
ÂÀÊ-2-115 |
50 |
220 |
1 |
2 |
14,5 |
115 |
2,2-21,75
2,2-24 |
109-121
57-138 |
±5 |
±2
±2 |
8
|
power duty
charging duty |
ÂÀÊ-6-115 |
50 |
220 |
1 |
6 |
21,75 |
115 |
2,2-21,75
2,2-24 |
109-121
57-138 |
±5
|
±2
±2 |
8
|
2 independent channels:
power
duty
charging duty |
ÂÀÊ-12-115 |
50 |
220/380 |
3 |
12
5,7 |
21,75
200 |
115
28,5 |
2,2-21,75
2,2-24
10-200
10-600 |
109-121
57-138
11-30
11-17 |
±5
|
±2
±2
±2 |
8
8
|
4 independent channels:
power
duty
charging duty
power
duty
start-up duty |
ÒÏÅ-200-28,5 |
50 |
220/380 |
3 |
5,7 |
200 |
28,5 |
10-200
5-50
5-50 |
22-30
2-33
2-33 |
2,5
2,5 |
±2 |
|
charging duty with current constancy
charging duty with voltage constancy |
ÒÏÅ-400-28,5 |
|
|
|
11,4 |
400 |
28,5 |
20-400
20-1200
20-400
10-100
10-100 |
11-30
11-17
22-30
2-33
2-33 |
5À
5À |
±2
±2
±2 |
8
|
power
duty
start-up duty
charging duty with current constancy
charging duty with voltage constancy |
ÒÏÅ-50-72-2 |
50 |
220/380 |
3 |
7,2 |
2õ50 |
72 |
2,5-50
2,5-50
3-63
2,5-50 |
2-72
12-72
2-72
72-2 |
1,25
|
±2
|
|
2 independent channels:
charging duty with current constancy
charging channels with voltage constancy
accelerated charge discharge AÁ |
ÒÏÑ-630ê |
50 |
380 |
3 |
630 |
2000 |
315 |
350-2500
100-2000 |
210-315
210-315 |
±5
|
±3 |
3 |
charging duty
power
duty |
ÂÀÊÇÑ-295-330 |
50 |
380 |
3 |
295 |
895 |
330 |
45-895
100-895 |
230-320
190-330 |
±7 |
±5
|
|
power
duty
charging duty |
ÂÀÊÇÑ-295-330 |
50 |
380 |
3 |
500 |
1500 |
330 |
75-1500
275-1500 |
230-320
190-330 |
±7 |
±5
|
3 |
power
duty
charging duty | |